Real documented commercial refrigeration and HVAC work by 2R Cooling across Port St. Lucie and the Treasure Coast — the project, findings, and work performed.

Called at 4:50 a.m. Sunday for a warm walk-in cooler at Berry Fresh in Stuart, 2R Cooling corrected a pressure-control issue and low refrigerant condition. After service, the KE2 controller displayed 37.8°F.

2R Cooling & Refrigeration repaired a failed glycol chiller at Ocean Republic Brewing in Stuart, Florida, correcting an issue with one of the chiller’s pressure switches, checking the electrical phases and performing additional system checks. This project documents the service visit with real equipment photos and feedback from the brewery’s head brewer.

2R Cooling & Refrigeration replaced the condensing unit serving an existing walk-in cooler at Nettles Island, Jensen Beach, Florida. With the existing evaporator retained, commissioning included detailed refrigeration troubleshooting, TXV and filter-drier replacement, and monitoring of cooling progress during pull-down.

2R Cooling replaced the locked compressor in the existing R22 walk-in cooler system at Francesca’s Pizza in the Gatlin area of Port St. Lucie, selecting a Tecumseh AKA9455EXD using Tecumseh’s replacement guidance.

2R Cooling responded to an emergency call at a Port St. Lucie supermarket where the entire refrigeration rack had shut off on its high-pressure safety switch. Troubleshooting isolated the cause to a faulty pressure transducer.

2R Cooling replaced a commercial walk-in cooler in Tequesta, from removal of the old enclosure to panel modification and sealing, one condensing unit, two evaporators, copper refrigerant piping and installation of ShieldVault at the cooler's refrigeration control panel. Explore the job through eleven real project photos.

2R Cooling repaired a commercial undercounter cooler at a restaurant in West Palm Beach by replacing its temperature probe and controller. Normal cooling was restored.

A beer-keg cooler at a Jensen Beach bar failed to cool. 2R Cooling replaced the failed fan motor, broken fan blade and damaged mounting bracket, then measured 35°F with Fieldpiece temperature probes.

Walk-in freezer repair at a Jensen Beach, FL food-service location. 2R Cooling replaced two failed fuses and identified a deteriorating condenser fan motor.

Commercial refrigeration repair in Port St. Lucie: 2R Cooling replaced a failed walk-in cooler condensing unit at Alfonso's Pizza with a Tecumseh 4,100 BTU R-404A medium-temperature unit, restoring cooler temperature from 44°F to 37°F.

Commercial walk-in cooler diagnosis in Stuart, Florida. 2R Cooling identified visibly heat-damaged electrical wiring and a contactor issue after the compressor failed to operate.

Walk-in freezer service at a senior-living facility in Boynton Beach. Service included defrost work and a same-model timer replacement. After the icing problem was corrected, a defrost thermostat fault was identified, with further control work planned.

Weekend emergency walk-in freezer service at Berry Fresh in West Palm Beach. 2R Cooling identified low refrigerant and added 3 pounds of R-404A. A follow-up leak search and a repair-versus-replacement evaluation are pending.

Commercial HVAC controls diagnosis in Melbourne, Florida. 2R Cooling found four rooftop-unit thermostats configured for the wrong remote-sensor type and corrected the configuration so each system controls from its actual zone temperature.

2R Cooling replaced a failed OEM condenser coil and liquid-line filter drier on a 6-ton Trane split-system condensing unit at a commercial retail facility in Fort Pierce, then pressure-tested, evacuated, charged and commissioned the system.