Commercial Refrigeration·Boynton Beach, Florida

Walk-In Freezer Repair in Boynton Beach: Evaporator Icing and Defrost Timer Replacement

Walk-in freezer service at a senior-living facility in Boynton Beach. Service included defrost work and a same-model timer replacement. After the icing problem was corrected, a defrost thermostat fault was identified, with further control work planned.

Project at a Glance

Location
Boynton Beach, Florida
Facility type
Senior-living facility kitchen
Equipment
Commercial walk-in freezer
Reported issue
Recurring evaporator frost/ice and warming
Work performed
Defrost, same-model defrost timer replacement, schedule adjustment
Planned follow-up
ShieldVault installation and thermostat issue follow-up
Contractor
2R Cooling & Refrigeration
Equipment
Commercial walk-in freezer
Customer type
Senior-living facility
Service
Walk-In Freezer Repair
Technician at the walk-in freezer's exterior controls during the defrost service visit.

Reported problem

The kitchen at a senior-living facility in Boynton Beach reported that its commercial walk-in freezer kept building frost and ice on the evaporator and was warming up. The service notes also recorded a warm, humid kitchen and frequent door openings during the day. Those operating conditions were noted as part of the service call; they were not established as the sole cause of the icing.

What we observed at the evaporator

  • Heavy frost and ice had built up on the evaporator coil, visibly obscuring the coil.
  • Frost was also present on the evaporator tubing near the existing expansion valve, which was inspected as part of the visit.
  • The existing defrost timer was an Intermatic DTAV40-series assembly.
Observed ice buildup covering the evaporator coil before defrost.
Frosted evaporator tubing and the existing expansion valve, inspected during the visit.

Work performed

  • Ran a defrost to clear the observed ice buildup; the coil fins were visibly cleared during service.
  • Replaced the defrost timer with a new timer of the same model (Intermatic DTAV40 series).
  • Adjusted the defrost schedule on the new timer.
  • Took temperature checks at the evaporator while the freezer was pulling back down after defrost.
Old and new Intermatic DTAV40-series defrost timers side by side during the replacement.
Coil fins and defrost elements visible after the ice was cleared during service.

Defrost thermostat finding and planned follow-up

After the icing problem was corrected, further troubleshooting identified a defrost thermostat that was not working and remained stuck open. A ShieldVault installation is planned as part of the follow-up control work. The thermostat issue and final operating result remain open items until that work is completed and verified.

Photos from the service visit

Temperature probe placed near the evaporator for checks during pull-down; some frost is still visible.
Evaporator front with fan guard and Fieldpiece probe during temperature testing.